Calculator

Voltage Drop Calculator

Calculate voltage drop, power loss, and actual voltage delivered to your load

Inputs

Distance from power source to load (not round-trip)

Select wire gauge - lower AWG = thicker wire

Current draw of your load in amperes

Voltage at the power source

Copper has lower resistance; aluminum is lighter and cheaper

Acceptable voltage drop

Critical electronics< 2%
General use< 3%
Non-critical loads< 5%
NEC maximum5%

3% drop at 12V

Voltage drop0.36V
Voltage at load11.64V

3% drop at 24V

Voltage drop0.72V
Voltage at load23.28V

How to use this calculator

  1. 1Enter the one-way wire length from your power source to the load (in feet)
  2. 2Select your wire gauge (AWG) - lower numbers mean thicker wire
  3. 3Enter the current draw of your load in amps
  4. 4Select your source voltage (12V, 24V, 48V DC, or 120V/240V AC)
  5. 5Choose your wire material (copper or aluminum)
  6. 6Review results: aim for under 3% voltage drop for most applications

Understanding voltage drop in electrical circuits

Voltage drop is one of the most critical considerations when designing any electrical system, especially low-voltage DC systems used in off-grid solar, RVs, boats, and emergency backup power. When current flows through a wire, some energy is lost due to the wire's resistance. This loss appears as a reduction in voltage at the load end and heat generated in the wire.

In 12V systems, voltage drop is especially critical. A 3% drop at 12V is only 0.36 volts - barely noticeable in calculations but significant in practice. Many 12V devices and batteries have tight operating ranges. LiFePO4 batteries, for example, have a flat discharge curve between 12.8V and 13.2V. Excessive voltage drop can push your system below safe operating thresholds, reducing efficiency and potentially damaging equipment.

The solution is proper wire sizing. Using thicker wire (lower AWG number) reduces resistance and voltage drop. However, thicker wire costs more and is harder to work with. Our voltage drop calculator helps you find the optimal wire gauge for your specific application, balancing cost, practicality, and electrical efficiency.

AWG wire resistance and ampacity (copper)

Wire GaugeOhms/1000ftMax Amps (chassis)
14 AWG3.0715A
12 AWG1.9320A
10 AWG1.2130A
8 AWG0.76440A
6 AWG0.49155A
4 AWG0.30870A
2 AWG0.19495A
1/0 AWG0.122125A
2/0 AWG0.0967145A
4/0 AWG0.0608195A

Voltage drop formula explained

The voltage drop formula for DC and single-phase AC circuits is:

VD = (2 × L × I × R) / 1000

Where VD is voltage drop in volts, L is one-way wire length in feet, I is current in amperes, and R is wire resistance in ohms per 1000 feet. The factor of 2 accounts for the round-trip distance (current flows to the load and back).

To calculate voltage drop percentage: divide the voltage drop by the source voltage and multiply by 100. For example, if you have a 0.5V drop in a 12V system: (0.5 / 12) × 100 = 4.17% voltage drop.

Power loss in watts is calculated as: P = VD × I (voltage drop multiplied by current). This represents energy wasted as heat in your wiring. In high-current applications, this can be substantial and is why efficient wire sizing matters for both safety and energy conservation.

12V voltage drop considerations

Low-voltage DC systems like 12V face unique challenges with voltage drop. Because the system voltage is already low, even small absolute voltage drops represent a significant percentage of the total voltage. Consider these examples:

Example 1: LED lighting circuit. A 12V LED strip drawing 5 amps, located 20 feet from the battery. Using 14 AWG copper wire: VD = (2 × 20 × 5 × 3.07) / 1000 = 0.61V. That's a 5.1% drop, resulting in only 11.39V at the LED strip. The lights will be noticeably dimmer. Upgrading to 10 AWG wire reduces the drop to 2.0% (0.24V), delivering 11.76V.

Example 2: Inverter connection. A 2000W inverter at 12V draws about 167 amps at full load. Even a 3-foot cable run requires heavy wire. With 4 AWG copper: VD = (2 × 3 × 167 × 0.308) / 1000 = 0.31V (2.6% drop). This is acceptable, but anything longer requires 2 AWG or larger.

Copper vs aluminum wire

When calculating voltage drop, wire material significantly affects results. Copper and aluminum are the two most common conductor materials, each with distinct characteristics.

Copper wire has approximately 61% lower resistance than aluminum of the same gauge. This means less voltage drop and smaller wire sizes for the same application. Copper is also more durable, easier to terminate, and has better corrosion resistance. For most DC applications, especially in vehicles, boats, and off-grid systems, copper is the standard choice.

Aluminum wire is lighter and less expensive than copper. It's commonly used in utility power lines and large commercial installations where weight and cost savings outweigh the need for smaller wire sizes. When using aluminum, you must size up approximately 2 AWG numbers to achieve the same voltage drop performance as copper (e.g., use 2 AWG aluminum instead of 4 AWG copper).

NEC guidelines and safety considerations

The National Electrical Code (NEC) provides guidelines for acceptable voltage drop in electrical installations. While the NEC allows up to 5% total voltage drop (3% for branch circuits + 2% for feeders), many professionals recommend staying well below these maximums for optimal system performance.

Safety considerations extend beyond voltage drop percentages. Wires carrying current generate heat proportional to I²R (current squared times resistance). Undersized wires can overheat, damaging insulation and creating fire hazards. Always ensure your wire gauge meets both voltage drop requirements AND ampacity ratings for the expected current.

For off-grid systems, consider using our wire gauge calculator in conjunction with this voltage drop calculator. The wire gauge calculator helps you select wire based on current capacity, while this calculator verifies that your choice also meets voltage drop requirements for your specific wire run length.

Reducing voltage drop in your system

If your calculated voltage drop is too high, you have several options to improve your system design:

1. Use larger wire. This is the most direct solution. Each step down in AWG number (larger wire) roughly halves the resistance and voltage drop. Going from 12 AWG to 10 AWG, for example, reduces resistance from 1.93 to 1.21 ohms per 1000 feet.

2. Shorten wire runs. Place batteries and power sources as close to loads as practical. In an RV or boat, centralizing the battery bank near high-current loads like inverters minimizes heavy wire runs.

3. Increase system voltage. Higher voltage systems carry the same power with less current. A 24V system carries 1000W at 42 amps versus 83 amps at 12V - half the current means roughly half the voltage drop for the same wire. This is why larger off-grid systems often use 24V or 48V.

4. Split loads across circuits. Instead of running one heavy wire to multiple loads, run separate smaller wires. This distributes current and can sometimes be more practical than running a single large cable.

Frequently asked questions

What is voltage drop and why does it matter?

Voltage drop is the reduction in voltage as electrical current travels through a wire. It matters because it reduces the power available to your devices and wastes energy as heat. Excessive voltage drop can cause motors to run poorly, lights to dim, and sensitive electronics to malfunction. In low-voltage DC systems like 12V, even small drops significantly impact performance.

What is an acceptable voltage drop percentage?

For most applications, keep voltage drop under 3%. Critical or sensitive electronics should have under 2%. The NEC (National Electrical Code) recommends a maximum of 5% total voltage drop for branch circuits, but 3% is preferred for efficiency. For 12V DC systems, 3% equals only 0.36V loss, which is why proper wire sizing is crucial.

How do I calculate voltage drop for a 12V system?

Use the formula: Voltage Drop = 2 x Length x Current x Resistance per foot. For a 12V system with 50 feet of 12 AWG copper wire carrying 10 amps: VD = 2 x 50 x 10 x 0.00193 = 1.93V (about 16% drop). This is too high! You would need 4 AWG wire to stay under 3% for this run.

Why is the wire length multiplied by 2?

The length is multiplied by 2 because electricity must travel to the load AND return to the source. A 50-foot run to a device is actually 100 feet of wire resistance (50 feet positive, 50 feet negative/ground). This round-trip distance is why voltage drop calculations use 2x the one-way distance.

Should I use copper or aluminum wire?

Copper has about 61% lower resistance than aluminum, making it the better choice for most DC applications where space is limited. Aluminum is lighter and cheaper, making it common in utility lines and large AC installations. For off-grid and mobile applications, copper is almost always preferred despite the higher cost.

What gauge wire do I need for a 12V 100 amp circuit?

For 100 amps at 12V, wire size depends heavily on distance. For a 3-foot run (typical battery to inverter), 2 AWG copper keeps voltage drop under 3%. For 10 feet, you need 1/0 AWG. For 25 feet, you would need 3/0 or 4/0 AWG. Always calculate based on your specific distance and acceptable voltage drop.

How does voltage affect wire size requirements?

Higher voltage systems require smaller wire for the same power. A 1000W load at 12V draws 83 amps, requiring heavy wire. The same 1000W at 24V draws only 42 amps, and at 48V just 21 amps. This is why 24V and 48V systems are preferred for higher power off-grid setups - they allow smaller, lighter, and cheaper wiring.

Can voltage drop cause a fire?

Yes, indirectly. While voltage drop itself does not cause fires, the conditions that create high voltage drop (undersized wire, high current) cause wires to heat up. This heat can damage insulation and potentially cause fires. Always use properly sized wire and fuses. If wires feel warm to the touch, they are undersized for the load.

How do I reduce voltage drop in my system?

You can reduce voltage drop by: 1) Using larger gauge (lower AWG number) wire, 2) Shortening wire runs by placing batteries closer to loads, 3) Upgrading to a higher voltage system (24V or 48V), 4) Using copper instead of aluminum, or 5) Splitting loads across multiple circuits. Often, a combination of these approaches works best.

What is the voltage drop formula?

The basic formula is: VD = (2 x L x I x R) / 1000, where VD is voltage drop in volts, L is one-way length in feet, I is current in amps, and R is wire resistance in ohms per 1000 feet. For percentage: VD% = (VD / Source Voltage) x 100. Our calculator handles all this math automatically based on your inputs.

Result

16.1%

Target: under 3% for most applications

Details

Voltage Drop1.9V
Voltage at Load10.1V
Power Loss in Wire19.3W